Series Blauberg Axis-Jet 60 Hz

Jet axial fans
Use
  • The Axis-Jet axial fans are designed for general purpose ventilation of underground and semiopened parkings, ventilation of tunnels, smoke extraction in case of fire as a part of smoke extract system. The fans generate a high-speed and high-pressure directed air jet.
  • Temperatures of the transported medium: in continuous operation up to +55 °C; in smoke extraction mode: 300 °C/2 hrs and 400 °C/2 hrs.
  • The fans with the fire resistance rating 200 °C/2 hrs can be manufactured on special request.
  • Functionality. Power. Efficiency.



Design
  • The casing of the Axis-Jet fan is made of polymer coated steel. The fans are available in two casing versions: cylindrical and octagonal.
  • The casing includes inner brackets for motor fixation. These brackets act as directing vanes and distribute air flow uniformly, thus increasing aerodynamic performances of the fan. The fan has a sound insulation of mineral wool.
  • The fan in an octagonal casing Axis-Jet-VI has a reduced height, a hinged hatch for electrical installation with captive bolts and a detachable middle part for maintenance.


Modifications
  • Unidirectional single-speed type (U).
  • Unidirectional double-speed type (U).
  • Reversible single-speed (R).
  • Reversible double-speed (R).



Motor
  • Three-phase asynchronous short-circuit rotor motor is installed inside the fan casing. Motor ingress protection rating is IP55. The motor design ensures operation of the fan in the smoke extract systems and/or general ventilation systems in unidirectional and reversible modes. The motors are designed for 400 V mains voltage and 60 Hz mains frequency.



Impeller
  • The dynamically balanced impeller is made of cast aluminium alloy (for fans of smoke extraction systems) or of glass-fiber reinforced polyamide (for fans of general industrial use).
  • The reversible fans are equipped with 100 % reversible two-directional impeller.



Mounting
  • The Axis-Jet fans are designed for horizontal ceiling mounting and fixation by means of the supplied fixing brackets attached to the fan casing.
Axis-Jet-CI axial jet fan design

Axis-Jet-VI axial jet fan design

Datasheet
Catalogue "Smoke extraction ventilation for parking premises (60 Hz)"
2.61 Mb
Datasheet
Axis-Jet (60 Hz) - data sheet
638 Kb
Manual
Axis-Jet (60 Hz) - user's manual
2.5 Mb
Certificates
BSI certificate 0086 CPR 784701 "Centro-Jet, Axis-Jet-CI, Axis-FP, Axis-RF"
1.14 Mb
Certificates
BSI certificate 2797 CPR 664983 "Centro-Jet, Axis-Jet-CI, Axis-FP, Axis-RF"
1.22 Mb
Image
Axis-Jet 60 Hz
367 Kb