Blauberg KOMFORT Roto EC SE 400 S21

Heat recovery air handling units
  • Power of electrical reheater: 1400 W
  • Maximum airflow: 440 m3/h
  • Sound pressure level LpA at 3 m: 33 dB(A)
  • Heat exchanger type: Rotary
  • Extract filter: G4
  • Supply filter: G4 + F7
  • Sound insulation
  • Motor type: EC
  • Reheater: Electric
  • BMS protocol: ModBus
  • Control: Smartphone
  • Casing material: Coated steel
  • Humidity sensor: Optional
  • CO2 sensor: Optional
  • VOC sensor: Optional
  • PM2.5 sensor: Optional
Unit of measurement KOMFORT Roto EC SE 400 S21
Connected air duct size mm 160
Phases - 1
Minimum supply voltage V 230
Maximum supply voltage V 230
Power supply frequency Hz 50/60
Rated power W 200
Power of electrical reheater W 1400
Unit current A 7.5
Maximum airflow m3/h 440
rotation speed at 50hz -
Sound pressure level LpA at 3 m dB(A) 33
Heat recovery efficiency, max % 85
Heat exchanger type - Rotary
Heat exchanger material - Aluminum
Weight kg 82
Extract filter - G4
Supply filter - G4 + F7
Transported air temperature (max) °С 40
Transported air temperature (min) °С -25
Ambient air temperature min °С 1
Ambient air temperature max °С 40
Ambient air humidity max % 80
Ingress protection rating - IP22
Ingress protection rating of the drive - IP44
Blauberg KOMFORT Roto EC SE 400 S21 54 400 2016
Trademark Blauberg
Model KOMFORT Roto EC SE 400 S21
Specific energy consumption (SEC) (kWh/(m2/a)) Cold Average Warm
84.9 A+ 41.8 A 17.1 E
Type of ventilation unit Bidirectional
Type of drive installed Variable speed
Type of heat recovery system Regenerative
Thermal efficiency of heat recovery (%) 81
Maximum flow rate (m3/h) 400
Electric power input (W) 170
Reference flow rate (m3/s) 0.076
Reference pressure difference (Pa) 50
Specific power input (SPI) (W/(m3/h)) 0.247
Control typology Local demand control
Maximum internal leakage rates (%) 2.7
Maximum external leakage rates (%) 2.7
Sound power level (dB(A)) 54
Declared typology RVU BVU
The annual electricity consumption (AEC) (kWh/a) Cold Average Warm
131 523 131
The annual heating saved (AHS) (kWh/a) Cold Average Warm
8817 4507 2038
Datasheet
KOMFORT Roto EC SE - data sheet
2.32 Mb
Manual
KOMFORT Roto EC S2(E)200 - user's manual
3.88 Mb
Manual
Modbus table for connecting S21 automation to BMS - user's manual (B55-8-1EN-02)
141 Kb
Manual
S21 - user's manual (B55-8EN-05)
626 Kb
Manual
KOMFORT Roto EC S(E)400(600) - user's manual (B140EN-04)
3.36 Mb
Manual
KOMFORT Roto EC S(E)280 - user's manual
2.37 Mb
Image
KOMFORT Roto EC SE 400 S21 - image 1
376 Kb
Ø D Ø D1 B H H1 L
160 100 528 675 755 747
Other accessories
Name Photo Description
Blauberg FP 436x196x40 G4 FP 436x196x40 G4 G4 panel filter
Blauberg FP 436x196x40 F7 FP 436x196x40 F7 F7 panel filter
Name Photo Description
Blauberg S22 S22 Control panels
Blauberg S22 Wi-Fi S22 Wi-Fi Control panels
Blauberg S25 S25 LCD control panel
Name Photo Description
Blauberg CD-1 CD-1 CO2 sensors
Blauberg CD-2 CD-2 CO2 sensors
Name Photo Description
Blauberg FS2 FS2 Humidity sensor
Other accessories
Name Photo Description
Blauberg DAH 251-13 DAH 251-13 Kitchen exhaust hood
Name Photo Description
Blauberg SD 160/600 SD 160/600 Silencers for round ducts
Blauberg SD 160/900 SD 160/900 Silencers for round ducts
Blauberg SD 160/1200 SD 160/1200 Silencers for round ducts
Name Photo Description
Blauberg VRV 160 VRV 160 Backdraft dampers with spring for round ducts
Blauberg VKA 160 VKA 160 Air dampers for round ducts