Blauberg KOMFORT ERV EC DB 100 L S14

Suspended heat and energy recovery air handling units
  • Sound pressure level LpA at 3 m: 30 dB(A)
  • Heat exchanger type: Cross flow
  • Extract filter: G4
  • Supply filter: G4 + F8 (PM2.5 > 93 %)
  • Sound-insulated casing
  • Motor type: EC
  • Enthalpy heat exchanger
  • Bypass: Manual
  • Control: Wired control panel
  • Casing material: Coated steel
  • Humidity sensor: Optional
  • CO2 sensor: Optional
Unit of measurement KOMFORT ERV EC DB 100 L S14
Phases - 1
Minimum supply voltage V 230
Maximum supply voltage V 230
Power supply frequency Hz 50/60
Rated power W 66
Unit current A 0.5
Maximum airflow m³/h 170
Sound pressure level LpA at 3 m dB(A) 30
Heat recovery efficiency, max % 82
Heat exchanger type - Cross flow
Heat exchanger material - Enthalpy
Weight kg 17
Extract filter - G4
Supply filter - G4 + F8 (PM2.5 > 93 %)
Transported air temperature (max) °С 40
Transported air temperature (min) °С -15
Ambient air temperature min °С 1
Ambient air temperature max °С 40
Ambient air humidity max % 60
Ingress protection rating - IP22
Ingress protection rating of the drive - IP44
Article - 8051692
Blauberg KOMFORT ERV EC DB 100 L S14 30 137 2016
Trademark Blauberg
Model KOMFORT ERV EC DB 100 L S14
Specific energy consumption (SEC) (kWh/(m²/a)) Cold Average Warm
-76.7 A+ -40 A -16.3 E
Type of ventilation unit Bidirectional
Type of drive installed Variable speed
Type of heat recovery system Recuperative
Thermal efficiency of heat recovery (%) 76
Maximum flow rate (m³/h) 137
Electric power input (W) 55
Reference flow rate (m³/s) 0.028
Reference pressure difference (Pa) 50
Specific power input (SPI) (W/(m³/h)) 0.273
Control typology Local demand control
Maximum internal leakage rates (%) 2.7
Maximum external leakage rates (%) 2.7
Declared typology RVU BVU
Sound power level (dB(A)) 30
The annual electricity consumption (AEC) (kWh/a) Cold Average Warm
726 189 144
The annual heating saved (AHS) (kWh/a) Cold Average Warm
8614 4403 1991
Datasheet
KOMFORT ERV EC DB - data sheet
1.23 Mb
Datasheet
KOMFORT ERV EC DB 100 S14 - energy label
54 Kb
Datasheet
KOMFORT ERV EC DB 100 S14 - specification
29 Kb
Manual
KOMFORT ERV EC DB - user's manual
3.64 Mb
BIM/CAD-models
KOMFORT ERV (EC) D(B)
2.18 Mb
Image
KOMFORT ERV EC DB 100 L S14 - image 1
237 Kb
D B H L L1
100 481 204 600 734
Name Photo Description
Blauberg VKA 100 VKA 100 Air dampers for round ducts
Name Photo Description
Blauberg CD-1 CD-1 CO2 sensors
Blauberg CD-2 CD-2 CO2 sensors
Name Photo Description
Blauberg FS2 FS2 Humidity sensor
Other accessories
Name Photo Description
Blauberg FP 200x191x20 G4 FP 200x191x20 G4 G4 panel filter