Blauberg AirWall

Blauberg AirWall - Single-room wall mounting HRV with high-efficiency HRV or ERV counter-flow recovery and app control. Cold-climate versions add integrated heaters plus mechanical supply and gravity exhaust dampers
Coming soon
Single-room wall mounting HRV with high-efficiency HRV or ERV counter-flow recovery and app control. Cold-climate versions add integrated heaters plus mechanical supply and gravity exhaust dampers
  • Sound pressure level LpA at 3 m: 34 dB(A)
  • Sound pressure level LpA at 1 m: 44 dB(A)
  • Heat exchanger type: Counter flow
  • Heat exchanger material: Polystyrene
  • Supply filter: Coarse 90% / G4
    Optional: ePM1 70% / F7
  • Extract filter: Coarse 90% / G4
  • Casing material: ABS Plastic
  • CO2 sensor: Optional
Unit of measurement AirWall
Speed - 1 2 3 4 5
Connected air duct size mm 250
Phases - 1
Maximum supply voltage V 230
Minimum supply voltage V 110
Rated power W 5 13 19 26 33
Unit current A 0.2
Maximum airflow m³/h 25 35 50 60 80
Maximum airflow (Boost mode) m³/h 125
Sound pressure level LpA at 3 m dB(A) 15 18 26 27 34
Sound pressure level LpA at 1 m dB(A) 26 28 36 38 44
Heat recovery efficiency % 90 87 84 80 75
Heat recovery efficiency, max % 90
Heat exchanger type - Counter flow
Heat exchanger material - Polystyrene
Weight kg 17
Supply filter - Coarse 90% / G4
Optional: ePM1 70% / F7
Extract filter - Coarse 90% / G4
Transported air temperature (max) °С 40
Transported air temperature (min) °С -20
Datasheet
AirWall leaflet 2026-06
239 Kb
Image
AirWall - image 1
308 Kb