Unit of measurement | VENTO Expert A50-1 W V.3 | |||
Minimum supply voltage | V | 100 | ||
Maximum supply voltage | V | 240 | ||
Power supply frequency | Hz | 50/60 | ||
Rated power | W | 5.00 | 6.00 | 8.50 |
Unit current | A | 0.035 | 0.040 | 0.059 |
Air flow in ventilation mode | m3/h | 15 | ||
Air flow in heat recovery mode | m3/h | 8 | ||
Sound pressure level LpA at 3 m | dB(A) | 4 | 16 | 28 |
Sound pressure level LpA at 1 m | dB(A) | 13 | 25 | 37 |
Heat recovery efficiency, max | % | 95 | ||
Heat exchanger type | - | Reversible | ||
Transported air temperature (max) | °С | 40 | ||
Transported air temperature (min) | °С | -20 | ||
Ambient air temperature min | °С | 1 | ||
Ambient air temperature max | °С | 40 | ||
Ambient air humidity max | % | 65 | ||
Ingress protection rating | - | IP24 |
Trademark | Blauberg | |||||
Model | VENTO Expert A50-1 W V.3 | |||||
Specific energy consumption (SEC) (kWh/(m2/a)) | Cold | Average | Warm | |||
-86.3 | A+ | -42.8 | A+ | -17.9 | E | |
Type of ventilation unit | Bidirectional | |||||
Type of drive installed | Variable speed | |||||
Type of heat recovery system | Regenerative | |||||
Thermal efficiency of heat recovery (%) | 85 | |||||
Maximum flow rate (m3/h) | 50 | |||||
Electric power input (W) | 8.5 | |||||
Reference flow rate (m3/s) | 0.01 | |||||
Specific power input (SPI) (W/(m3/h)) | 0.186 | |||||
Control typology | Local demand control | |||||
Airflow sensitivity at +20 Pa and -20 Pa (%) | 0.3 | |||||
The indoor/outdoor air tightness (m3/h) | 4 | |||||
Declared typology | RVU BVU | |||||
Sound power level (dB(A)) | 47 | |||||
The annual electricity consumption (AEC) (kWh/a) | Cold | Average | Warm | |||
108 | 108 | 108 | ||||
The annual heating saved (AHS) (kWh/a) | Cold | Average | Warm | |||
89 | 46 | 21 |
Name | Photo | Description |
---|---|---|
Blauberg SE Vento Expert W | Control panel |
Name | Photo | Description |
---|---|---|
Blauberg CD-1 | CO2 sensors | |