Blauberg Reneo S 351 L S14

Blauberg Reneo S 351 L S14 - Heat and energy recovery air handling units
Coming soon
Heat and energy recovery air handling units
  • Maximum airflow: 410 m3/h
  • Sound pressure level LpA at 3 m: 26 dB(A)
  • Heat exchanger type: Counter flow
  • Extract filter: Coarse > 60 %
  • Supply filter: Coarse > 60 % (option: ePM1 60 %)
  • Sound insulation
  • Motor type: EC
  • Bypass: Manual
  • Control: Wired control panel
  • Casing material: EPP
  • Humidity sensor: Optional
  • CO2 sensor: Optional
Unit of measurement Reneo S 351 L S14
Connected air duct size mm 160
Phases - 1
Minimum supply voltage V 230
Maximum supply voltage V 230
Power supply frequency Hz 50/60
Rated power W 213
Unit current A 1.62
Maximum airflow m3/h 410
Sound pressure level LpA at 3 m dB(A) 26
Heat recovery efficiency, max % 93
Heat exchanger type - Counter flow
Heat exchanger material - Polystyrene
Weight kg 26
Extract filter - Coarse > 60 %
Supply filter - Coarse > 60 % (option: ePM1 60 %), Coarse > 60 % (option: ePM1 60 %)
Transported air temperature (max) °С 40
Transported air temperature (min) °С -25
Ambient air temperature min °С 1
Ambient air temperature max °С 40
Ambient air humidity max % 60
Ingress protection rating - IP22
Ingress protection rating of the drive - IP44
Blauberg Reneo S 351 L S14 46 360 2016
Trademark Blauberg
Model Reneo S 351 L S14
Specific energy consumption (SEC) (kWh/(m2/a)) Cold Average Warm
82.6 A+ 43 A+ 17.8 E
Type of ventilation unit Bidirectional
Type of drive installed Variable speed
Type of heat recovery system Recuperative
Thermal efficiency of heat recovery (%) 90
Maximum flow rate (m3/h) 360
Electric power input (W) 213
Reference flow rate (m3/s) 0.071
Reference pressure difference (Pa) 50
Specific power input (SPI) (W/(m3/h)) 0.26
Control typology Local demand control
Maximum internal leakage rates (%) 2.7
Maximum external leakage rates (%) 2.7
Sound power level (dB(A)) 46
Declared typology RVU BVU
The annual electricity consumption (AEC) (kWh/a) Cold Average Warm
720 183 138
The annual heating saved (AHS) (kWh/a) Cold Average Warm
9181 4693 2122
Datasheet
Reneo S 350 - data sheet
1.65 Mb
Manual
S21 - user's manual (B55-8EN-05)
626 Kb
Manual
S14 - user's manual (B55-7EN-02)
1.31 Mb
Manual
Reneo S 350/550 - user's manual (B279EN-02)
8.99 Mb
Image
Reneo S 351 L S14 - image 1
709 Kb
Ø D H H1 L L1 W W1
160 880 939 616 230 770 355
Other accessories
Name Photo Description
Blauberg FP 496x150x60 Coarse 90% G4 FP 496x150x60 Coarse 90% G4 G4 panel filter
Blauberg FP 496x150x60 ePM1 65% F7 FP 496x150x60 ePM1 65% F7 F7 panel filter
Other accessories
Name Photo Description
Blauberg EP-Reneo S 351 EP-Reneo S 351 Decorative panel
Name Photo Description
Blauberg FS2 FS2 Humidity sensor
Name Photo Description
Blauberg CD-3
Blauberg CD-1 CD-1 CO2 sensors
Blauberg CD-2 CD-2 CO2 sensors
Name Photo Description
Blauberg SFK 20x32 SFK 20x32 Hydraulic syphon for condensate drainage
Name Photo Description
Blauberg SD 160/600 SD 160/600 Silencers for round ducts
Blauberg SD 160/900 SD 160/900 Silencers for round ducts
Blauberg SD 160/1200 SD 160/1200 Silencers for round ducts
Name Photo Description
Blauberg VKA 160 VKA 160 Air dampers for round ducts
Name Photo Description
Blauberg Belimo TF230 Belimo TF230 Electric actuators