Blauberg KOMFORT EC DB 250 L S21

Suspended heat recovery air handling units
  • Maximum airflow: 270 m3/h
  • Sound pressure level LpA at 3 m: 28 dB(A)
  • Heat exchanger type: Counter flow
  • Extract filter: G4
  • Supply filter: F7
  • Sound insulation
  • Motor type: EC
  • Bypass: Auto
  • Reheater: Optional
  • Preheater: Optional
  • BMS protocol: ModBus
  • Control: Smartphone
  • Casing material: Galvanized steel
  • Humidity sensor: Optional
  • CO2 sensor: Optional
  • VOC sensor: Optional
  • PM2.5 sensor: Optional
Unit of measurement KOMFORT EC DB 250 L S21
Connected air duct size mm 125
Phases - 1
Minimum supply voltage V 230
Maximum supply voltage V 230
Power supply frequency Hz 50/60
Rated power W 101
Unit current A 0.8
Maximum airflow m3/h 270
Sound pressure level LpA at 3 m dB(A) 28
Heat recovery efficiency, max % 98
Heat exchanger type - Counter flow
Heat exchanger material - Polystyrene
Weight kg 48
Extract filter - G4
Supply filter - F7
Transported air temperature (max) °С 40
Transported air temperature (min) °С -25
Ambient air temperature min °С 1
Ambient air temperature max °С 40
Ambient air humidity max % 80
Ingress protection rating - IP22
Ingress protection rating of the drive - IP44
Blauberg KOMFORT EC DB 250 L S21 49 237 2016
Trademark Blauberg
Model KOMFORT EC DB 250 L S21
Specific energy consumption (SEC) (kWh/(m2/a)) Cold Average Warm
78.9 A+ 41 A 15.2 E
Type of ventilation unit Bidirectional
Type of drive installed Variable speed
Type of heat recovery system Recuperative
Thermal efficiency of heat recovery (%) 82
Maximum flow rate (m3/h) 237
Electric power input (W) 100
Reference flow rate (m3/s) 0.052
Reference pressure difference (Pa) 50
Specific power input (SPI) (W/(m3/h)) 0.293
Control typology Local demand control
Maximum internal leakage rates (%) 2.7
Maximum external leakage rates (%) 2.7
Sound power level (dB(A)) 49
Declared typology RVU BVU
The annual electricity consumption (AEC) (kWh/a) Cold Average Warm
737 200 155
The annual heating saved (AHS) (kWh/a) Cold Average Warm
8261 4223 1909
Datasheet
KOMFORT EC DB - data sheet
1.41 Mb
Datasheet
KOMFORT EC DB 250 S21 - energy label
96 Kb
Datasheet
KOMFORT EC DB 250 S21 - specification
76 Kb
Manual
KOMFORT EC DB - user's manual (B108EN-05)
4.32 Mb
Manual
Modbus table for connecting S21 automation to BMS - user's manual (B55-8-1EN-02)
141 Kb
Manual
S21 - user's manual (B55-8EN-05)
626 Kb
BIM/CAD models
KOMFORT EC DB 250 - BIM model
1.01 Mb
Image
KOMFORT EC DB 250 L S21 - image 1
324 Kb
ØD B H H1 L
125 754 320 361 1008
Other accessories
Name Photo Description
Blauberg FP 403x253x48 G4 FP 403x253x48 G4 G4 panel filter
Blauberg FP 403x253x48 F7 FP 403x253x48 F7 F7 panel filter
Name Photo Description
Blauberg S22 S22 Control panels
Blauberg S22 Wi-Fi S22 Wi-Fi Control panels
Blauberg S25 S25 LCD control panel
Name Photo Description
Blauberg FS2 FS2 Humidity sensor
Name Photo Description
Blauberg CD-1 CD-1 CO2 sensors
Blauberg CD-2 CD-2 CO2 sensors
Name Photo Description
Blauberg EVH 125-0.6-1 S21 V.2 EVH 125-0.6-1 S21 V.2 Electric duct preheater for heat exchanger freeze protection
Blauberg EVH 125-0.8-1 S21 V.2 EVH 125-0.8-1 S21 V.2 Electric duct preheater for heat exchanger freeze protection
Blauberg EVH 125-1.2-1 S21 V.2 EVH 125-1.2-1 S21 V.2 Electric duct preheater for heat exchanger freeze protection
Blauberg ENH 125-0.6-1 S21 V.2 ENH 125-0.6-1 S21 V.2 Duct heater for supply air reheating
Blauberg ENH 125-0.8-1 S21 V.2 ENH 125-0.8-1 S21 V.2 Duct heater for supply air reheating
Blauberg ENH 125-1.2-1 S21 V.2 ENH 125-1.2-1 S21 V.2 Duct heater for supply air reheating
Name Photo Description
Blauberg SFK 20x32 SFK 20x32 Hydraulic syphon for condensate drainage
Name Photo Description
Blauberg SD 125/600 SD 125/600 Silencers for round ducts
Blauberg SD 125/900 SD 125/900 Silencers for round ducts
Blauberg SD 125/1200 SD 125/1200 Silencers for round ducts
Name Photo Description
Blauberg VKA 125 VKA 125 Air dampers for round ducts
Name Photo Description
Blauberg Belimo TF230 Belimo TF230 Electric actuators