Unit of measurement | Iso-Primo 355 | |||
Connected air duct size | mm | 355 | ||
Phases | - | 1 | ||
Minimum supply voltage | V | 230 | ||
Maximum supply voltage | V | 230 | ||
Power supply frequency | Hz | 50 | ||
Rated power | W | 126 | 131 | 150 |
Unit current | A | 0.60 | 0.58 | 0.66 |
Maximum airflow | m3/h | 1986 | 2170 | 2360 |
rotation speed at 50hz | - | 1350 | 1400 | 1470 |
Sound pressure level LpA at 3 m | dB(A) | 1350 | 1400 | 1470 |
Weight | kg | 20.7 | ||
Transported air temperature (max) | °С | 55 | ||
Transported air temperature (min) | °С | -25 | ||
Ambient air temperature min | °С | 1 | ||
Ambient air temperature max | °С | 40 | ||
Ingress protection rating | - | IPX4 | ||
Ingress protection rating of the drive | - | IP20 |
Trademark | Blauberg |
Model | Iso-Primo 355 |
Type of ventilation unit | Unidirectional |
Type of drive installed | Integrated VSD |
Type of heat recovery system | None |
Nominal flow rate (m3/s) | 0.457 |
Nominal external pressure (Pa) | 129 |
Maximum external leakage rates (%) | 2.7 |
Static efficiency (%) | 41.8 |
Effective electric power input (kW) | 0.144 |
Sound power level (dB(A)) | 58 |
Declared typology | NRVU UVU |
Name | Photo | Description |
---|---|---|
Blauberg SD 355/600 | Silencers for round ducts | |
Blauberg SD 355/900 | Silencers for round ducts | |
Blauberg SD 355/1200 | Silencers for round ducts |
Name | Photo | Description |
---|---|---|
Blauberg VKA 355 | Air dampers for round ducts |
Name | Photo | Description |
---|---|---|
Blauberg CDP-3/5 | Multi-speed switch |
Name | Photo | Description |
---|---|---|
Blauberg CDT1 E1.5 | Multi-speed switches | |
Blauberg CDT E1.8 | Thyristor speed controller | |
Blauberg CDTE E3.0 TP | Speed controllers |