Blauberg Iso-Mix 200 TUSW1

Sound-insulated inline mixed-flow fans
  • Maximum airflow: 1035 m3/h
  • Sound pressure level LpA at 3 m: 36 dB(A)
  • Sound insulation
  • Motor type: AC
  • Control: Built-in speed controller
  • Impeller type: Mixed-flow
  • Casing material: Coated steel
  • Installation in any position
  • Cable with mains plug
  • Timer: Turn off timer
Unit of measurement Iso-Mix 200 TUSW1
Connected air duct size mm 200
Phases - 1
Minimum supply voltage V 230
Maximum supply voltage V 230
Power supply frequency Hz 50/60
Rated power W 82 100 110
Unit current A 0.37 0.44 0.49
Maximum airflow m3/h 731 961 1035
rotation speed at 50hz - 2376 2382 2445
Sound pressure level LpA at 3 m dB(A) 30 34 36
Weight kg 8
Transported air temperature (max) °С 60
Ingress protection rating - IPX4
Ingress protection rating of the drive - IP44
Trademark Blauberg
Model Iso-Mix 200 TUSW1
Specific energy consumption (SEC) (kWh/(m2/a)) Cold Average Warm
52.8 A+ 25.7 C 10.2 E
Type of ventilation unit Unidirectional
Type of drive installed Multi-speed
Type of heat recovery system None
Maximum flow rate (m3/h) 800
Electric power input (W) 110
Reference flow rate (m3/s) 0.156
Reference pressure difference (Pa) 50
Specific power input (SPI) (W/(m3/h)) 0.139
Control typology Local demand control
Maximum external leakage rates (%) 2.7
Sound power level (dB(A)) 33
Declared typology RVU UVU
The annual electricity consumption (AEC) (kWh/a) Cold Average Warm
104 104 104
The annual heating saved (AHS) (kWh/a) Cold Average Warm
5536 2830 1280
Datasheet
Iso-Mix - data sheet
1.14 Mb
Datasheet
Iso-Mix 200 - specification
34 Kb
Manual
Iso-Mix 200 - user's manual (B97-2EN-01)
2.87 Mb
Manual
Iso-Mix (355-400-450) - user's manual
3.91 Mb
Manual
Iso-Mix (100-315) - user's manual (B97EN-06)
3.99 Mb
Certificates
Iso-Mix - certificate LVD
136 Kb
Certificates
Iso-Mix - certificate GS
226 Kb
Image
Iso-Mix 200 TUSW1 - image 1
501 Kb
ØD B B1 L H
198 293 386 550 295
Name Photo Description
Blauberg MLCD E2 MLCD E2 Room temperature regulator
Name Photo Description
Blauberg CDP-2/5 CDP-2/5 Multi-speed switch
Blauberg CDP-3/5 CDP-3/5 Multi-speed switch
Blauberg CDP-2/10 CDP-2/10 Multi-speed switch
Name Photo Description
Blauberg CDT E0.5 CDT E0.5 Thyristor speed controller
Blauberg CDT E1.8 CDT E1.8 Thyristor speed controller
Blauberg CDT1 E0.5 CDT1 E0.5 Multi-speed switches
Name Photo Description
Blauberg TE / TI 1.5 TE / TI 1.5 Timers
Blauberg HSE / HSI 1.5 HSE / HSI 1.5 Sensors
Blauberg LSE / LSI 1.5 LSE / LSI 1.5 Sensors
Blauberg IRSE / IRSI 1.5 IRSE / IRSI 1.5 Sensors
Name Photo Description
Blauberg KFBT 200 G4 KFBT 200 G4 Filter boxes with pocket filters for round ducts
Blauberg KFBK 200 KFBK 200 Filter boxes for round ducts
Blauberg KFBT 200 F5 KFBT 200 F5 Filter boxes with pocket filters for round ducts
Blauberg KFBT 200 F7 KFBT 200 F7 Filter boxes with pocket filters for round ducts
Name Photo Description
Blauberg SD 200/1200 SD 200/1200 Silencers for round ducts
Blauberg SD 200/900 SD 200/900 Silencers for round ducts
Blauberg SD 200/600 SD 200/600 Silencers for round ducts
Name Photo Description
Blauberg EKH 200-1.2 EKH 200-1.2 Duct electrical heaters for round ducts
Blauberg EKH 200-1.7 EKH 200-1.7 Duct electrical heaters for round ducts
Blauberg EKH 200-2.0 EKH 200-2.0 Duct electrical heaters for round ducts
Blauberg EKH 200-2.4 EKH 200-2.4 Duct electrical heaters for round ducts
Blauberg EKH 200-3.4 EKH 200-3.4 Duct electrical heaters for round ducts
Blauberg EKH 200-3.6 EKH 200-3.6 Duct electrical heaters for round ducts
Blauberg EKH 200-5.1 EKH 200-5.1 Duct electrical heaters for round ducts
Blauberg EKH 200-6.0 EKH 200-6.0 Duct electrical heaters for round ducts
Name Photo Description
Blauberg WKH 200-2 WKH 200-2 Duct water heaters for round ducts
Blauberg WKH 200-4 WKH 200-4 Duct water heaters for round ducts
Name Photo Description
Blauberg VRV 200 VRV 200 Backdraft dampers with spring for round ducts
Blauberg VKA 200 VKA 200 Air dampers for round ducts