Series Blauberg BSK2...72S

Normally open fire-resisting duct damper with a mechanical drive mechanism
Use
  • The fire dampers are intended for automatic closing of process openings and air duct penetrations in intermediate floors, walls and partitions, as well as closing of openings in supply and exhaust ducts of smoke ventilation systems.
  • The dampers of this particular design are not suitable for installation in air ducts and ducts of premises with rated explosion and fire safety category A and B and in flammable and explosive mixture intakes. The BSK2...72S fire-resisting duct dampers are capable of resisting fire for at least 120 minutes (EI 120) at the temperature of 600 °C.



Design
  • The BSK2...72S series dampers are made in the general-purpose industrial version with a minimized variety of hardware components using low-alloy galvanized steel. The damper flap is made of fire-resistant material.
  • The duct installation design results in two mounting flanges on the casing for integration into a ventilation ducts (air ducting) and external configuration of the drive mechanism for easier maintenance.

Control and modifications
  • The BSK2...72S series dampers are equipped with a mechanical actuating unit with a thermal fuse and a return spring.
  • The damper is set to the operating position upon the thermal fuse breakdown resulting from a temperature increase. The damper can then be re-set to the protective position only manually by using a handle and by replacing the thermal fuse through the access hole.
  • Emergency damper actuation: the flap remains in protective position (damper unaffected by fire) and is fixed by a thermal fuse (when the flap is installed in security position, a reverse spring is activated). Upon emergency actuation (damper directly affected by fire) the thermal fuse breaks down and the return spring moves the flap to operating position.


The BSK2...72S fire safety damper with a mechanical actuating unit with a thermal fuse and a return spring
Datasheet
Catalogue "Fire safety dampers"
7.71 Mb
Datasheet
BSK2 - data sheet
1.51 Mb
Manual
BSK - user's manual (B58-1EN-04)
3.68 Mb
Image
BSK2...72S
602 Kb