Blauberg KOMFORT Roto EC D2E 250 L S21

Suspended heat recovery air handling units
  • Power of electrical reheater: 700 W
  • Maximum airflow: 300 m3/h
  • Sound pressure level LpA at 3 m: 23 dB(A)
  • Heat exchanger type: Rotary
  • Extract filter: G4
  • Supply filter: G4
  • Sound insulation
  • Motor type: EC
  • Reheater: Electric
  • BMS protocol: ModBus
  • Control: Smartphone
  • Casing material: Galvanized steel
  • Humidity sensor: Optional
  • CO2 sensor: Optional
  • VOC sensor: Optional
  • PM2.5 sensor: Optional
Unit of measurement KOMFORT Roto EC D2E 250 L S21
Connected air duct size mm 160
Phases - 1
Minimum supply voltage V 230
Maximum supply voltage V 230
Power supply frequency Hz 50/60
Rated power W 128
Power of electrical reheater W 700
Unit current A 4
Maximum airflow m3/h 300
Sound pressure level LpA at 3 m dB(A) 23
Heat recovery efficiency, max % 87
Heat exchanger type - Rotary
Heat exchanger material - Aluminum
Weight kg 54
Extract filter - G4
Supply filter - G4, F7 (option: H13), G4, F7 (опция: H13)
Transported air temperature (max) °С 40
Transported air temperature (min) °С -25
Ambient air temperature min °С 1
Ambient air temperature max °С 40
Ambient air humidity max % 80
Ingress protection rating - IP22
Ingress protection rating of the drive - IP44
Blauberg KOMFORT Roto EC D2E 250 L S21 45 230 2016
Trademark Blauberg
Model KOMFORT Roto EC D2E 250 L S21
Specific energy consumption (SEC) (kWh/(m2/a)) Cold Average Warm
84.8 A+ 41.7 A 17 E
Type of ventilation unit Bidirectional
Type of drive installed Variable speed
Type of heat recovery system Regenerative
Thermal efficiency of heat recovery (%) 81
Maximum flow rate (m3/h) 230
Electric power input (W) 89
Reference flow rate (m3/s) 0.044
Reference pressure difference (Pa) 50
Specific power input (SPI) (W/(m3/h)) 0.256
Control typology Local demand control
Maximum internal leakage rates (%) 2.7
Maximum external leakage rates (%) 2.7
Sound power level (dB(A)) 45
Declared typology RVU BVU
The annual electricity consumption (AEC) (kWh/a) Cold Average Warm
136 136 136
The annual heating saved (AHS) (kWh/a) Cold Average Warm
8817 4507 2038
Datasheet
KOMFORT Roto EC DE S21 - data sheet
1.68 Mb
Datasheet
KOMFORT Roto EC D2E 250 S21 - energy label
99 Kb
Datasheet
KOMFORT Roto EC D2E 250 S21 - specification
82 Kb
Manual
KOMFORT Roto EC D - user's manual (B158EN-05)
3.53 Mb
Manual
S21 - user's manual (B55-8EN-05)
626 Kb
Manual
Modbus table for connecting S21 automation to BMS - user's manual (B55-8-1EN-02)
141 Kb
BIM/CAD models
KOMFORT Roto EC DE(D2E) 250 R(L) S21 - BIM model
1.03 Mb
Image
KOMFORT Roto EC D2E 250 L S21 - image 1
308 Kb
Ø D Ø D1 B B1 H H1 L L1
160 125 618 666 225 245 1002 1097
Other accessories
Name Photo Description
Blauberg FP 280x180x48 G4 FP 280x180x48 G4 G4 panel filter
Blauberg FP 280x180x48 F7 FP 280x180x48 F7 F7 panel filter
Blauberg FP 280х180х48 H13
Name Photo Description
Blauberg S22 S22 Control panels
Blauberg S22 Wi-Fi S22 Wi-Fi Control panels
Blauberg S25 S25 LCD control panel
Name Photo Description
Blauberg FS2 FS2 Humidity sensor
Other accessories
Name Photo Description
Blauberg DAH 251-13 DAH 251-13 Kitchen exhaust hood
Name Photo Description
Blauberg VRV 160 VRV 160 Backdraft dampers with spring for round ducts
Blauberg VKA 160 VKA 160 Air dampers for round ducts