Induction centrifugal fans Centro-Jet are designed for general purpose ventilation of underground and semiopened parkings, smoke extraction in case of fire as a part of smoke extract system. The fans generate a high-speed and high-pressure directed air jet.
The fans with the fire resistance rating 200 °C/2 hrs can be manufactured on special request.
Modifications
Single-speed.
Double-speed.
Motor
Single- or double-speed 4-, 6- or 8-pole asynchronous motors are used. The motor ingress protection rating is IP55. The motors are rated for 400 V power mains voltage and 50 Hz frequency.
Design
Centro-Jet casing is made of polymer coated steel.
Due to low height of the casing the fan is recommended for use in low-ceilinged room.
The protecting grille on the intake side prevents ingress of foreign objects into the fan.
Deflector plates on the exhaust side of the fan ensure correct air flow distribution.
Impeller
The impeller with backward curved steel blades.
Mounting
The Centro-Jet fans are designed for ceiling mounting and fixation by means of the supplied fixing brackets. Power is supplied through the internal terminal box. The fan wiring and mounting must be made according to the instructions and the wiring diagram shown in the terminal box.