Series Blauberg PRD

Pressure control valves
Use
  • The PRD excess pressure relief valves are used in smoke protection, ventilation and air conditioning systems to regulate the pressure difference between adjacent rooms. The product meets the requirements of EN 121101-6:2005 “Smoke protection systems. Part 6: Technical requirements for pressure difference systems”.
  • When calculating air pressure systems, air leaks through open doors, openings, and other gaps shall be taken into account. When these are closed, the pressure difference between the protected space (lobbies, stairwells, elevator shafts, etc.) and the fire zone can reach critical levels.
  • To balance the pressure difference in these spaces and make sure doors on escape routes can be opened easily (standard handle force — no more than 100 N), a PRD valve must be installed.


Mounting
  • The PRD pressure control valve is made of galvanised steel with a rectangular cross-section.
  • The product is available with two flanges for direct connection to air ducts or with a single flange for installation in a wall.


Design
  • The valve can only be mounted in a vertical position and all the axes of the operating plates (blades) must be oriented horizontally.
  • A spring mechanism located on the front side of the product acts as the control element.
  • Adjustment takes place during the commissioning of the smoke ventilation system and is performed directly by compressing the operating spring until the required trigger pressure is achieved.
  • The pressure control range is 20-150 Pa.
  • There are no requirements for thermal conductivity or leakage class.


Datasheet
PRD - data sheet
234 Kb
Image
PRD - image 1
584 Kb