| Unit of measurement | Box-R 200 V2 | ||
| Speed | - | 1 | 2 |
| Minimum supply voltage | V | 230 | |
| Maximum supply voltage | V | 230 | |
| Power supply frequency | Hz | 50 | |
| Rated power | W | 103 | 142 |
| Unit current | A | 0.45 | 0.63 |
| Maximum airflow | m3/h | 770 | 1200 |
| Sound pressure level LpA at 3 m | dB(A) | 46 | 48 |
| Weight | kg | 8.8 | |
| Transported air temperature (max) | °С | 50 | |
| Ingress protection rating | - | IPX4 | |
| Ingress protection rating of the drive | - | IP44 | |
| Impeller material | - | Plastic | |
| Trademark | Blauberg | |||||
| Model | Box-R 200 V2 | |||||
| Specific energy consumption (SEC) (kWh/(m2/a)) | Cold | Average | Warm | |||
| -51.8 | A+ | -24.8 | C | -9.3 | F | |
| Type of ventilation unit | Unidirectional | |||||
| Type of drive installed | Variable speed | |||||
| Type of heat recovery system | None | |||||
| Maximum flow rate (m3/h) | 551 | |||||
| Electric power input (W) | 123 | |||||
| Reference flow rate (m3/s) | 0.107 | |||||
| Reference pressure difference (Pa) | 50 | |||||
| Specific power input (SPI) (W/(m3/h)) | 0.267 | |||||
| Control typology | Local demand control | |||||
| Maximum external leakage rates (%) | 2.7 | |||||
| Sound power level (dB(A)) | 66 | |||||
| Declared typology | RVU UVU | |||||
| The annual electricity consumption (AEC) (kWh/a) | Cold | Average | Warm | |||
| 141 | 141 | 141 | ||||
| The annual heating saved (AHS) (kWh/a) | Cold | Average | Warm | |||
| 5536 | 2830 | 1280 | ||||
| Name | Photo | Description |
|---|---|---|
| Blauberg CDP-2/5 |
|
Multi-speed switch |
| Blauberg CDP-3/5 |
|
Multi-speed switch |
| Blauberg MLCD E2 |
|
Room temperature regulator |
| Name | Photo | Description |
|---|---|---|
| Blauberg HSE / HSI 1.5 |
|
Sensors |
| Blauberg TE / TI 1.5 |
|
Timers |
| Blauberg LSE / LSI 1.5 |
|
Sensors |
| Blauberg IRSE / IRSI 1.5 |
|
Sensors |