Blauberg BLS02 RV 2500

Floor mounted heat recovery units
  • Sound pressure level LpA at 3 m: 36 dB(A)
  • Heat exchanger type: Rotary
  • Heat exchanger material: Aluminium/aluminium with hygroscopic coating
  • Supply filter: ePM1 70% (ISO 16890)-F7 (EN779)
  • Extract filter: ePM1 70% (ISO 16890)-F7 (EN779)
  • Sound-insulated casing
  • Preheater: Optional
  • Reheater: Optional
  • BMS protocol: ModBus
  • Control: Wired control panel
  • Casing material: Aluzinc steel
Unit of measurement BLS02 RV 2500
Casing performance - 50 mm, T2/TB2
Connected air duct size mm 500x250
Phases - 3
Minimum supply voltage V 380
Maximum supply voltage V 400
Power supply frequency Hz 50/60
Rated power supply fan W 1200
Rated power extract fan W 1200
Unit current A 4.3
Maximum airflow m³/h 2850
Maximum airflow at ESP 200 Pa m³/h 2700
Sound pressure level LpA at 3 m dB(A) 36
Heat exchanger type - Rotary, condensation or enthalpy
Heat exchanger material - Aluminium/aluminium with hygroscopic coating
Weight kg 365
Supply filter - ePM1 70% (ISO 16890)-F7 (EN779)
Extract filter - ePM1 70% (ISO 16890)-F7 (EN779)
Transported air temperature (max) °С 40
Transported air temperature (min) °С -25
Ambient air temperature max °С 60
Ambient air temperature min °С -40
Ingress protection rating - IP22
Ingress protection rating of the drive - IP54
Datasheet
Catalogue "Compact units BlauAIR"
4 Mb
Datasheet
BlauAIR RV - data sheet
463 Kb
Manual
BlauAIR RV - user's manual (B192-4EN-02)
1.45 Mb
Manual
Liquid heat exchanger HW/CW - installation instruction (B234-2EN-01)
2.01 Mb
Manual
DX cooler CDX - installation instruction (B234-3EN-01)
1.27 Mb
Manual
BlauAIR automatic control system (S37, S38, S39, S49) - user's manual (B280EN-04)
4.85 Mb
Manual
Modbus table for connecting S31, S37 automation to BMS - user's manual (B297EN-01)
562 Kb
Manual
BlauAIR automatic control system (S29, S30, S31, S32) - user's manual (B201EN-03)
5.74 Mb
Image
BLS02 RV 2500 - image 1
763 Kb