| Unit of measurement | Axis-QR 400 4D | ||
| Phases | - | 3 | |
| Minimum supply voltage | V | 400 | |
| Maximum supply voltage | V | 400 | |
| Power supply frequency | Hz | 50 | 60 |
| Rated power | W | 180 | |
| Unit current | A | 0.47 | |
| Maximum airflow | m3/h | 3740 | |
| Sound pressure level LpA at 3 m | dB(A) | 54 | |
| Weight | kg | 8.5 | |
| Transported air temperature (max) | °С | 60 | |
| Transported air temperature (min) | °С | -30 | |
| Ingress protection rating | - | IP24 | |
| Ingress protection rating of the drive | - | IP54 | |
| Impeller material | - | Coated steel | |
| Article | - | 8013560 | |
| Trademark | Blauberg |
| Model | Axis-QR 400 4D |
| Type of drive installed | External MSD or VSD |
| Type of heat recovery system | None |
| Nominal flow rate (m3/s) | 0.78 |
| Nominal external pressure (Pa) | 90 |
| Maximum external leakage rates (%) | 2.7 |
| Static efficiency (%) | 34.3 |
| Sound power level (dB(A)) | 84 |
| Effective electric power input (kW) | 0.209 |
| Declared typology | NRVU UVU |