| Unit of measurement | AirWall E ERV | |||||
| Speed | - | 1 | 2 | 3 | 4 | 5 |
| Connected air duct size | mm | 250 | ||||
| Phases | - | 1 | ||||
| Maximum supply voltage | V | 230 | ||||
| Minimum supply voltage | V | 220 | ||||
| Rated power | W | 5 | 10 | 15 | 24 | 46 |
| Power of electrical preheater | W | 200 | ||||
| Unit current | A | 0.28 | ||||
| Maximum airflow | m³/h | 25 | 35 | 50 | 60 | 80 |
| Maximum airflow (Boost mode) | m³/h | 150 | ||||
| Sound pressure level LpA at 3 m | dB(A) | 11 | 13 | 17 | 21 | 27 |
| Sound pressure level LpA at 1 m | dB(A) | 21 | 23 | 27 | 31 | 36 |
| Heat recovery efficiency, max | % | 85 | ||||
| Heat exchanger type | - | Counter flow | ||||
| Heat exchanger material | - | Enthalpy | ||||
| Weight | kg | 17 | ||||
| Supply filter | - | Coarse 90% / G4 Optional: ePM1 70% / F7 |
||||
| Extract filter | - | Coarse 90% / G4 | ||||
| Transported air temperature (max) | °С | 40 | ||||
| Transported air temperature (min) | °С | -20 | ||||
| Minimum wall thickness | mm | 160 | ||||
| Maximum wall thickness | mm | 760 | ||||