Blauberg VENTO Expert A50-1 Pro

Heat recovery single-room units
  • Air flow in heat recovery mode: 25 m3/h
  • Sound pressure level LpA at 3 m: 21 dB(A)
  • Sound pressure level LpA at 1 m: 30 dB(A)
  • Filter: G3 (option: pollen filter)
  • In sound-insulated casing
  • Motor type: EC
  • Enthalpy heat exchanger
  • Control: Remote Control
  • Shutters
Unit of measurement VENTO Expert A50-1 Pro
Connected air duct size mm 160
Minimum supply voltage V 100
Maximum supply voltage V 230
Power supply frequency Hz 50/60
Rated power W 3.61 4.15 5.2
Unit current A 0.025 0.03 0.039
Air flow in ventilation mode m3/h 15 30 50
Air flow in heat recovery mode m3/h 8 15 25
Rotation speed at 50hz - 800 1300 1900
Sound pressure level LpA at 3 m dB(A) 11 18 21
Sound pressure level LpA at 1 m dB(A) 20 27 30
Heat recovery efficiency, max % 93
Heat exchanger material - Ceramic
Filter - G3 (option: pollen filter)
Transported air temperature (max) °С 40
Transported air temperature (min) °С -20
Ambient air temperature min °С 1
Ambient air temperature max °С 40
Ambient air humidity max % 80
Ingress protection rating - IP24
Blauberg VENTO Expert A50-1 Pro 38 50 2016
Trademark Blauberg
Model VENTO Expert A50-1 Pro
Specific energy consumption (SEC) (kWh/(m2/a)) Cold Average Warm
-83.1 A+ -41.3 A -17.3 E
Type of ventilation unit Bidirectional
Type of drive installed 3-speed
Type of heat recovery system Regenerative
Thermal efficiency of heat recovery (%) 77
Maximum flow rate (m3/h) 50
Electric power input (W) 5.2
Reference flow rate (m3/s) 0.004
Specific power input (SPI) (W/(m3/h)) 0.138
Control typology Local demand control
Maximum internal leakage rates (%) 2.7
Mixing rate (%) 1
Airflow sensitivity at +20 Pa and -20 Pa (%) 0.4
The indoor/outdoor air tightness (m3/h) 0.5
Declared typology RVU BVU
Sound power level (dB(A)) 38
The annual electricity consumption (AEC) (kWh/a) Cold Average Warm
100 100 100
The annual heating saved (AHS) (kWh/a) Cold Average Warm
86 44 20
Datasheet
VENTO Expert A50-1 Pro - data sheet
485 Kb
Manual
VENTO Expert A50-1 Pro - user's manual
9.2 Mb
Manual
Outer ventilation hood with frost protection AH-8 - installation instruction (B113-10EN-02)
1.14 Mb
Manual
Filters maintenance manual
3.18 Mb
Image
VENTO Expert A50-1 Pro - image 1
240 Kb
Other accessories
Name Photo Description
Blauberg FB Vento Expert A50 FB Vento Expert A50 Remote control
Name Photo Description
Blauberg PP 160/0.5 PP 160/0.5 The outer hood is designed to prevent the ingress of water and large objects into the ventilation equipment from outside
Other accessories
Name Photo Description
Blauberg CD-1 CD-1 CO2 sensors
Blauberg CD-2 CD-2 CO2 sensors